Engineering Guides · Module 03
Electrical protection and thermal management
Protect the wire first, the converter second and the load third. Heat is the loss times the thermal resistance.
Assumptions: Numbers in the examples are illustrative and the code is executed by the site’s tests. Type and characteristic summaries are general engineering knowledge; always confirm values on the datasheet of the part you use.
1. Engineering problem
Faults are certain over a robot’s life: shorts, reversed connectors, stalled motors, blocked fans. Protection limits the damage; thermal design keeps normal operation below component limits.
2. When is this needed?
- During the electrical design.
- When a motor or converter runs hot.
- Before field operation.
3. Selection and design decisions
Common protections: fuse or circuit breaker at the source, reverse-polarity protection, inrush limiting for large capacitors, over- and under-voltage cutoff in the BMS, a hardware emergency stop that removes motor power independent of software, and temperature sensing.
| Protection | Protects against |
|---|---|
| Main fuse near the battery | Short circuit in the harness |
| Branch fuses | A fault on one branch |
| Reverse polarity (diode, MOSFET, keyed connector) | Wrong battery connection |
| Pre-charge or inrush limiter | Contact welding and sparks on connection |
| BMS cut-off | Cell over- and under-voltage, over-current |
| Hardware emergency stop | Hazardous motion: removes drive power without software |
| Temperature sensing | Overheating of motors, drivers and batteries |
4. Advantages and disadvantages
- Fuse speed and rating: too small blows on start-up; too large does not protect the wire.
- Passive cooling is silent and sealed; fans move more heat and add dust ingress and a failure point.
- Derating keeps parts cooler and lengthens life at a cost in size.
5. Requirements and constraints
- Fuse current rating below the wire rating; voltage rating above the pack voltage.
- The emergency stop does not depend on the main computer.
- Every part stays below its datasheet maximum temperature at the highest ambient in the ODD.
6. Architecture
battery ─▶ main fuse ─▶ contactor / e-stop ─▶ branch fuses ─▶ loads
temperature sensors ─▶ controller ─▶ derate or stop7. Implementation
- List the faults to survive (short, reverse connection, stall, blocked cooling).
- Place the protection near the source of each branch.
- Estimate the loss in each part and the steady temperature: ΔT = P × Rth (thermal resistance from the datasheet).
- Estimate motor winding temperature from the resistance rise if you can measure it (below).
- Test: trip each protection on purpose in a safe setup and confirm the robot reaches a safe state.
alpha = 0.00393
def winding_temp(r_cold, t_cold, r_hot):
return (r_hot / r_cold - 1) / alpha + t_cold
print(f"winding temperature: {winding_temp(0.50, 20.0, 0.62):.1f} C")
rth, p = 4.0, 12.0
print(f"steady rise with {rth} K/W and {p} W: {rth * p:.0f} K, at 30 C ambient -> {30 + rth * p:.0f} C")Printed (checked by the site’s tests):
winding temperature: 81.1 C
steady rise with 4.0 K/W and 12.0 W: 48 K, at 30 C ambient -> 78 CReading it: copper’s resistance rises about 0.393 % per °C (a standard handbook temperature coefficient, 0.00393 per °C, not sourced from a document here). A winding that measured 0.50 Ω at 20 °C and 0.62 Ω now is at about 81 °C. A part with 4 K/W thermal resistance dissipating 12 W rises 48 K, so it reaches 78 °C in a 30 °C ambient. Values are illustrative.
8. Real examples
- AMR: main fuse at the battery, BMS cut-off, a hardware e-stop contactor in series with the motor drivers, and a thermistor on each motor.
9. Failure scenarios
- E-stop implemented only in software.
- A fuse with a voltage rating below the pack voltage failed to clear a short.
- Thermal estimate done at 20 °C ambient for a robot used at 40 °C.
10. Troubleshooting
- If a fuse blows, find the fault before replacing it.
- If the motor is hot, compare the winding temperature estimate with the datasheet limit.
- If a fan fails, check the thermal margin without it.
11. Validation
- The example prints the values above (executed by the site tests).
- Each protection was triggered in test and the robot reached a safe state.
- Steady temperatures are below limits at the highest ambient in the ODD.
12. Engineering checklist
13. Further references
- Datasheets of the fuses, converters, motors and batteries (voltage rating, thermal resistance, maximum temperature). Machine safety requirements for the e-stop depend on the applicable standard for your robot and are not covered here.