Design & Selection · Module 04
Choosing a communication interface
Pick the interface from data rate, distance, number of nodes and noise, then confirm the payload rate leaves margin.
Assumptions: Numbers in the examples are illustrative and the code is executed by the site’s tests. Facts taken from a cited source are marked; other statements are general engineering knowledge and must be confirmed on the datasheet of the part you use.
1. Engineering problem
Every sensor and actuator needs a link to the controller. The wrong choice shows up as lost data, noise sensitivity or a bus that cannot be extended. A quick payload-rate calculation removes most wrong choices before any hardware is bought.
2. When is this needed?
- When selecting a new sensor, motor driver or controller board.
- When adding a device to an existing bus.
- When a link drops data and you need to know whether it is overloaded or noisy.
3. Selection and design decisions
General characteristics (the facts marked as sourced come from Wikipedia: classic CAN carries 8 bytes per frame and CAN FD up to 64; CAN uses a twisted pair terminated with 120 Ω at each end; common I²C speeds are 100 and 400 kbit/s with a 7-bit address and pull-up resistors; SPI is full-duplex with an active-low select line per device). The rest is general engineering knowledge; confirm on the datasheets.
| Interface | Topology | Typical use | Watch for |
|---|---|---|---|
| UART | Point to point | GNSS receivers, simple modules, debug | No addressing; baud-rate error; no built-in error recovery |
| SPI | One controller, one select line per device | IMUs, ADCs, flash at high rate | Short wires; extra select line per device; mode must match |
| I²C | Shared two-wire bus with 7-bit addresses | Slow sensors, EEPROMs | Pull-up value and bus capacitance; address clashes; clock stretching |
| CAN / CAN FD | Multi-drop twisted pair, 120 Ω at both ends | Motor drivers, battery, actuators over metres | Termination, bit timing, bus load |
| Ethernet | Switched, point to point | LiDAR, cameras, computers | Switch bandwidth, PTP support, connectors |
| USB | Host with hubs | Cameras, adapters | Hub power, cable length, host controller sharing |
4. Advantages and disadvantages
- Simplicity vs robustness: UART is trivial to wire and weak at noise and errors; CAN is differential with error detection but needs termination and configuration.
- Rate vs distance: faster signalling shortens the usable cable length.
- Shared vs dedicated links: a shared bus saves wiring and couples devices (one faulty node can disturb all).
5. Requirements and constraints
- Required payload rate ≤ 70 % of the link’s usable payload rate (a design margin, not a standard).
- Cable length and environment match the signalling (differential for noisy, long runs).
- The controller has the peripheral and the driver support for the interface.
6. Architecture
sensor/actuator ──link (UART | SPI | I²C | CAN | Ethernet | USB)──▶ controller or computer ──▶ ROS 2 driver node7. Implementation
- List each device with its required data rate in bit/s.
- Compute the usable payload rate of each candidate link (below).
- Keep only links where the need is ≤ 70 % of the payload rate.
- Filter by distance, noise, number of nodes and driver support.
- Write the choice and the numbers in the interface control document.
def uart_payload_bps(baud, data_bits=8, parity=0, stop=1):
frame = 1 + data_bits + parity + stop # start + data + parity + stop bits
return baud * data_bits / frame
def i2c_payload_bps(clock_hz):
return clock_hz * 8 / 9 # 8 data bits + 1 ACK bit per byte; addressing overhead ignored
need = {"imu": 0.2e6, "gps": 0.04e6, "lidar": 90e6} # required bit/s
links = {"UART 115200": uart_payload_bps(115200), "UART 921600": uart_payload_bps(921600), "I2C 400k": i2c_payload_bps(400e3)}
for name, rate in need.items():
ok = [l for l, c in links.items() if rate <= 0.7 * c]
print(name, "fits:", ok or "none of these links")Printed (checked by the site’s tests):
imu fits: ['UART 921600', 'I2C 400k']
gps fits: ['UART 115200', 'UART 921600', 'I2C 400k']
lidar fits: none of these linksReading it: a UART frame of 8 data bits with one start and one stop bit carries 8 payload bits per 10 line bits, so 115200 baud gives about 92 kbit/s of payload; I²C sends 9 clock cycles per byte (8 data bits and an acknowledge bit), so 400 kHz gives about 356 kbit/s before addressing overhead. A 0.2 Mbit/s IMU stream does not fit 115200 baud with margin, a 90 Mbit/s LiDAR fits none of these links (it needs Ethernet). Rates are illustrative.
8. Real examples
- Mobile robot: IMU over SPI to a microcontroller, motor drivers on CAN, LiDAR on Ethernet, GNSS on UART.
9. Failure scenarios
- An IMU configured at a data rate that exceeds a 115200 baud UART, so samples are silently dropped.
- Two I²C devices with the same address.
- A CAN bus without termination.
10. Troubleshooting
- If data is lost, compare the measured rate with the payload rate and the 70 % limit.
- If errors appear only when motors run, suspect noise and look at the cabling guide.
- If a device does not answer, check address, mode, voltage level and pull-ups.
11. Validation
- The fit check above prints the lines shown (executed by the site tests).
- Measured message rate equals the configured rate with no gaps over the longest mission.
12. Engineering checklist
13. Further references
- Wikipedia, UART, SPI and I²C, read 2026-11-06 (secondary sources; the I²C specification itself was not read).
- Wikipedia, CAN bus and CAN FD, read 2026-11-06 (secondary source; the standards are ISO 11898, which was not read).